    Adaptive Protection and Control in Power System for Wide-Area Blackout Prevention

    Get PDF
    This paper presents a new approach in adaptive outof-step (OOS) protection settings in power system in real-time. The proposed method uses extended equal area criterion (EEAC) to determine the critical clearing time (CCT) and critical clearing angle (CCA) of the system, which are vital information for OOS protection setting calculation. The dynamic model parameters and the coherency groups of the system for EEAC analysis are determined in real time to ensure that the newly calculated settings suit with the prevalent system operating condition. The effectiveness of the method is demonstrated in a simulated data from 16-machine 68-bus system model

    Estimating Dynamic Model Parameters for Adaptive Protection and Control in Power System

    Get PDF

    Effect of promoter strength and signal sequence on the periplasmic expression of human interferon- &#9452b in Escherichia coli

    Get PDF
    Two plasmids, pFLAG-ATS and pET 26b(+), were studied for the periplasmic expression of recombinant human interferon-2b (IFN-2b) in Escherichia coli. The pFLAG-ATS contains ompA signal sequence and tac promoter while pET 26b(+) contains pelB signal sequence and T7lac promoter. It was observedthat periplasmic expression of IFN-2b from pET 26b(+) was around 3000 times higher than pFLAGATS. Difference in the expression level was attributed to the difference in the promoters and the signal sequences. In silico analysis of mRNA secondary structures were analyzed using Vienna RNA packageand MFOLD. The results suggested that the increase of expression would mainly due to the difference in the translation initiation associated with secondary structure of mRNA transcribed by both plasmids

    Coherency Identification in Interconnected Power Systems - An Independent Component Analysis Approach

    Get PDF
    This paper presents a novel approach to the coherency identification technique in interconnected power system using independent component analysis (ICA). The ICA is applied to the generator speed and bus angle data to identify the coherent areas of the system. The results of the application of ICA using simulated data from 16-machine 68-bus system model and on data gathered through U.K. University-based Wide-Area Measurement System are presented. The approach is able to identify the cluster of generators and buses following a disturbance in the system. It is also demonstrated that the approach is robust in the presence of noise in measured signal, which is an important factor to be considered for assessing the effectiveness of any measurement-based technique

    Estimating dynamic model parameters for adaptive protection and control in power system

    No full text
    Summary form only given. This paper presents a new approach in estimating important parameters of power system transient stability model such as inertia constant H and direct axis transient reactance xprimed in real time. It uses a variation of unscented Kalman filter (UKF) on the phasor measurement unit (PMU) data. The accurate estimation of these parameters is very important for assessing the stability and tuning the adaptive protection system on power swing relays. The effectiveness of the method is demonstrated in a simulated data from 16-machine 68-bus system model. The paper also presents the performance comparison between the UKF and EKF method in estimating the parameters. The robustness of method is further validated in the presence of noise that is likely to be in the PMU data in reality